Products / Control cables – for normed safety / H05VVC4V5-K

Usage

Control cables approved in accordance with HAR and UL.

H05VVC4V5-K are control cables in accordance with VDE 0281 Part 13 in a shielded version. They can be used in both dry and wet rooms but not outdoors.

H05VVC4V5-K cables may be permanently or flexibly laid with free movement and without compulsory ducting.

H05VVC4V5-K cables are preferred for use in machine engineering as connection and connecting cables for control, measurement and regulation purposes, on conveyor belts, in assembly areas of industrial robot technology and all related sectors. The range also meets the current safety guidelines for installation in washing systems, filling stations, breweries and similar applications.

Properties

The shielding made from tin-plated copper wire braiding is applied over an inner sheath. The effectiveness of the shield is represented by the coupling resistance and lies under 250 mOhm/m at 30 MHz.

H05VVC4V5-K cables have black cores with sequential numbering and a green-yellow earth conductor. With a relatively short twisted length that does not exceed the 15-fold diameter of the stranding layer, the cables are designed specifically for flexible, place-changing uses. They have no extended, power carrying core as a basic principle.

The outer sheath is made using a high-quality, special, oil-proof, mixture in accordance with VDE 0281 Part 1. In accordance with this, the outer sheath must withstand extreme conditions (7 x 24 hours at 90° C in an aggressive test oil IRM 902). This shows that use is possible in places where other sheath qualities are not able to handle the multi-faceted chemical influences over time.

Technical data

Download datasheet
Conductor Temperature range
Litz fine copper wire, not insulated according to VDE 0295
class 5 / IEC 228 class 5
In motion -5° C up to +70° C, still up to -30° C
Insulation Flame retardancy
PVC TI 2 according to VDE 0281 Part 1 IEC 332.1 or VDE 0482 Part 0265-2-1
Core identifier Bending radius
Black cores with white numbers, earth conductor green-yellow 12 x D (cable diameter)
Stranding Conductor resistance
Cores concentric in layer, twisted length a  maximum of 15 times the cable diameter;  stranding band without extended, power-carrying core See Technical information
Inner sheath Test voltage
PVC TM 1/2 according to VDE 0281 Part 1 Effective 3,000 Volts
Shielding Nominal voltage
Entire sheath made from tin-plated, braided copper wire with an optical density of at least 80 % 300/500 Volts
Sheath Breakdown voltage
Special PVC TM 5
According to VDE 0281 Part 1 (oil-proof)
Default colour, grey RAL 7001
Minimum 6,000 Volts
Norms Resilience up to 30° C
According to or based on
VDE 0281, 0293, 0295, 0472, 0473, 0482
See Technical information

The product conforms to the 2006/95/EU directive ("low voltage directive") CE.