Products / Control cables – for normed safety / A07VVH6-F

Usage

Harmonised PVC cables in flat construction. According to version, approved for 500 or 750 Volts.

The cables are ideally suited to the connection of place-changing and often moved power consumers with a medium or high mechanical loads, for example, for transportation and conveyor systems, tools, lifts, lifting gear etc. (lifts of up to 35 m hanging length with a maximum travel speed of 1.6 m/second).

Properties

The cables have a green-yellow earth conductors identified by the label G.

Technical data

Download datasheet
Conductor Flame retardancy
Litz fine copper wire, not insulated according to VDE 0295
class 5 / IEC 228 class 5

Special
Litz finest copper wire, not insulated  according to VDE 0295
class 6 / IEC 228 class 6
IEC 332.1 or VDE 0482 Part 0265-2-1
Insulation Bending radius
PVC TI 2 according to VDE 0281 Part 1 10 x D (cable thickness)
Core identifier Conductor resistance
Colour-coded up to 5-cores
As of 6-cores, black with white numbers (in accordance with VDE 0293), earth conductor green-yellow
See Technical information
Core arrangement Test voltage
cores are arranged in parallel and in groups of up to 5 cores Effective 3,000-5,000 Volts according to cross-section
Sheath Nominal voltage
PVC TM 1/2 according to VDE 0281 Part 1

Special
PVC TM 4 according to VDE 0281 Part 1,  cold-proof
Default colour, black RAL 9005
H05VVH6-F - U0/U 300/500 Volts
H07VVH6-F - U0/U 450/750 Volts
Norms Breakdown voltage
According to or based on
VDE 0281, 0293, 0295, 0472, 0473, 0482
EN 50214
Minimum 6,000 Volts
Temperature range Resilience up to 30° C
In motion -5° C up to +70° C, still up to -30° C

Special
In motion -30° C up to +70° C, still up to -40° C
See Technical information

The product conforms to the 2006/95/EU directive ("low voltage directive") CE.